How much ventilation does an open-flued boiler need?
As a rule of thumb from BS 5440-2, an open-flued appliance in a room needs 5 cm² of free vent area per kW of net input above 7 kW — so an 18 kW net appliance needs (18 − 7) × 5 = 55 cm². Compartments need vents at both high and low level: 10 cm² per kW if vented to a room, or 5 cm² per kW if vented to outside.