Skip to main content
Electrical

Schedule of Test Results Explained

The schedule of test results is the row-by-row record of every circuit you tested — read across one row and you should be able to see, at a glance, that the circuit is safe and compliant.

Updated 24 Aug 20269 min read

Behind every Electrical Installation Certificate and condition report sits a schedule of test results: a table with a row per circuit and a column for each measurement. It is where the numbers live, and it is the evidence that the inspection and testing were actually carried out rather than merely declared.

This guide walks through every column on a typical schedule — the circuit details, the continuity and ring-final values, insulation resistance, polarity, measured Zs, RCD operation and the functional checks — and explains what each one records and why it belongs there.

Key takeaways

  • The schedule has one row per circuit and a column for each test, so a complete row demonstrates a safe circuit.
  • Circuit details capture the conductor csa and the protective device type, rating and BS number.
  • Continuity is recorded as R1+R2 (or R2), and ring finals additionally record r1, rn and r2 end-to-end readings.
  • Insulation resistance, polarity and measured Zs confirm the circuit is sound and disconnection will occur.
  • RCD figures (the ×1 and ×5 disconnection times, plus the test-button check) and functional tests complete the picture.

Circuit details

The left-hand columns describe the circuit before any test result appears. They identify the circuit, its function and the conductors: the cross-sectional area (csa) of the live conductors and of the circuit protective conductor, so the reader knows what was installed. Alongside that sit the protective device details — its type, its rating in amps and the BS number of the device.

These details are not filler. The Zs limit a circuit must meet, the sizing checks and the RCD expectations all depend on the type and rating of the protective device, so recording them accurately is what makes the rest of the row meaningful.

Record the device, not just the reading

TradePlanr lets you enter the circuit details and each test value as you work and issue the certificate PDF on site — the device type and rating drive the limits the readings are checked against, so they need to be right.

Continuity and ring-final values

Continuity confirms the conductors are unbroken and correctly connected. For most circuits this is recorded as R1+R2 — the combined resistance of the line and protective conductors — or as R2 alone where that method is used. A sound, low reading tells you the earth path is intact end to end.

Ring final circuits get extra columns because they need extra proof that the ring is genuinely a ring. The r1, rn and r2 end-to-end readings — line, neutral and protective conductor measured around the loop — are recorded so that a broken or interconnected ring shows up in the figures rather than hiding as a healthy-looking radial.

Insulation resistance, polarity and Zs

Insulation resistance is recorded (in megohms) to show the insulation between conductors, and between conductors and earth, is healthy and not leaking. A high value passes; a low one warns of breakdown. Polarity is confirmed and recorded to prove that line, neutral and earth are connected the right way round throughout — that switching and protection are in the line conductor, not the neutral.

The measured Zs column records the earth fault loop impedance actually measured at the circuit. It is checked against the maximum permitted for that protective device: if the measured Zs is within the limit, enough fault current will flow to disconnect the supply in the required time. This is one of the most important figures on the whole schedule.

RCD and functional tests

Where a circuit is RCD-protected, the schedule records how the device performed. The ×1 test applies the rated residual current and records the disconnection time; the ×5 test applies five times the rated current and records the (faster) disconnection time, confirming the RCD trips quickly under a larger fault. The integral test button is also operated to confirm the mechanical trip works.

Finally, functional tests confirm that switchgear, controls and the like operate as intended. Together with the electrical readings, the functional column completes the row — the whole point being that a fully filled-in row is a self-contained demonstration that the circuit is safe and compliant.

The columns at a glance

The table below lists the columns you would expect on a typical schedule of test results and what each one records.

ColumnWhat it records
Circuit detailsCircuit reference and function, live and cpc conductor csa, and the protective device type, rating and BS number.
Continuity (R1+R2 or R2)Combined line-and-cpc resistance, or cpc resistance alone, confirming conductors are continuous and connected.
Ring (r1 / rn / r2)End-to-end line, neutral and cpc readings on ring final circuits, proving the ring is intact and correctly wired.
Insulation resistanceResistance in megohms between conductors and to earth, confirming insulation is sound.
PolarityConfirmation that line, neutral and earth are correctly connected and protection is in the line conductor.
Zs (measured)The earth fault loop impedance measured at the circuit, checked against the maximum for the protective device.
RCD (×1, ×5, test button)Disconnection times at rated and five-times rated residual current, plus operation of the integral test button.
FunctionalConfirmation that switchgear, controls and protective devices operate as intended.
Schedule of test results — columns and what they record

Frequently asked questions

What is R1+R2 on the schedule?

It is the combined resistance of the line conductor (R1) and the circuit protective conductor (R2), measured to confirm continuity of the earth path. Some inspectors record R2 alone instead, depending on the test method used.

Why do ring circuits have r1, rn and r2 columns?

A ring final needs proof it is genuinely a continuous ring. The end-to-end line (r1), neutral (rn) and cpc (r2) readings reveal a broken or interconnected ring in the figures, which a simple continuity check alone might miss.

What do the RCD ×1 and ×5 tests show?

The ×1 test applies the rated residual current and records the disconnection time; the ×5 test applies five times that current and records the faster time under a larger fault. Both confirm the RCD trips within the required limits.

From guidance to action

Related guides

Start Now — It's Free

Free to start · No card · No download needed — works in your browser

Download on the App StoreGet it on Google Play