Guidance & standards
The method follows the coordination requirements of BS 7671:2018+A2: the cable's tabulated rating, after derating for its installation conditions, must be at least the rating of the device protecting it. The factors used are Ca from Table 4B1 (thermoplastic), Cg from Table 4C1 for bunched circuits, Ci from Table 52.2 for cable in thermal insulation, and the 0.725 factor applied where a BS 3036 rewirable fuse provides overload protection.
The suggested size uses the current-carrying capacities for 70°C thermoplastic flat twin and earth installed to Reference Method C — clipped direct — from Table 4D5 (for example 27A for 2.5mm², 37A for 4mm², 47A for 6mm²). Other installation methods carry less current: the same cable in conduit, in a stud wall or above a plasterboard ceiling has a lower rating, so treat the suggestion as a starting point and check the correct column for your actual method.
Where several factors apply, they multiply, and the required It climbs quickly — a 32A device with two grouped circuits at 40°C already needs It ≥ 46A. Note that grouping and insulation factors generally apply to the section of route where the condition exists; where conditions differ along the route, size for the worst section.
Current-carrying capacity is only one leg of the design. The chosen cable still needs checking for voltage drop, earth fault loop impedance and shock protection, and the adiabatic equation where relevant. Guidance only — always verify against BS 7671 and the On-Site Guide for the actual installation method.
Suggestion uses Table 4D5 Method C (clipped direct) — other installation methods carry less current. Guidance only — always verify against BS 7671 and the On-Site Guide for the actual installation method.