Guidance & standards
The voltage drop limits used here follow BS 7671:2018+A2 for installations supplied directly from a public low-voltage network: 3% for lighting and 5% for other uses, which at 230V nominal works out to 6.9V and 11.5V respectively. The calculator applies whichever limit matches the circuit type you select.
The mV/A/m figures are for 70°C thermoplastic (PVC) flat twin and earth only, per Table 4D5. If you are running SWA, singles in conduit, or cable at a different conductor operating temperature, the tabulated values differ and this tool will not give the right answer. Long runs at high load can also justify a temperature-corrected voltage drop calculation, which this simple check does not perform.
Voltage drop is only one part of circuit design. A cable that passes on volt drop must still be checked for current-carrying capacity with correction factors, earth fault loop impedance and, where relevant, the adiabatic equation. Use this tool alongside the cable sizing and max Zs calculators rather than instead of a full design.
As with all these tools: guidance only. Verify the final design against BS 7671 and the On-Site Guide for the actual installation method.
70°C flat twin & earth mV/A/m values (Table 4D5). Guidance only — always verify against BS 7671 and the On-Site Guide for the actual installation method.