Skip to main content

kW to Amps Calculator (Single and Three Phase)

Convert
Supply
Result

Guidance only — always verify against current standards and manufacturer instructions.

Get all 48 calculators in your pocket

The TradePlanr app puts this calculator — plus gas & electrical certificates, quoting, invoicing and job sign-offs — on your phone, working even with no signal. Free to start — works in your browser, no download needed.

Download on the App StoreGet it on Google Play

This converter changes power in kilowatts into current in amps — and back again — for UK 230V single-phase and 400V three-phase supplies, with power factor taken into account. Electricians use it constantly: turning an appliance's kW rating into the design current for a circuit, or a measured current into the load in kW.

For single phase the tool divides the power by the voltage and power factor; for three phase it uses the line voltage with the √3 factor that accounts for the three-phase relationship. Enter the value, choose the direction and supply, set the power factor (1 for resistive loads such as heaters), and read off the result.

The formula

1φ: I = (kW × 1000) / (230 × pf) 3φ: I = (kW × 1000) / (√3 × 400 × pf)

I is the current in amps and kW × 1000 converts the power to watts. For single phase, the divisor is the 230V supply voltage multiplied by the power factor (pf). For three phase, the divisor is √3 (about 1.732) times the 400V line voltage times the power factor, which gives the current per line for a balanced load. Power factor is 1 for purely resistive loads such as heaters and showers, and less than 1 for motors and similar loads — a lower power factor means more current for the same useful power. The A → kW direction simply inverts the same equations.

How to use it

  1. 1

    Choose the direction

    Select kW → A to find the current a load draws, or A → kW to convert a measured current into power.

  2. 2

    Choose the supply

    Pick single phase (230V) or three phase (400V). Three-phase results are the current per line for a balanced load.

  3. 3

    Enter the value and power factor

    Type in the kW or amps figure and the power factor — leave it at 1 for resistive loads like showers and heaters, or use the nameplate power factor for motors.

Guidance & standards

The conversion assumes the UK nominal voltages of 230V single phase and 400V three phase, and a balanced load across phases for three-phase calculations. Real supply voltage varies within tolerance, so measured currents will differ slightly from calculated ones.

Power factor matters for anything with windings or electronics. A 5.5kW motor at a power factor of 0.85 draws around 9.3A per phase on a 400V supply, not the 7.9A a unity calculation gives — undersizing on that difference is a classic error. Appliance nameplates usually state full-load current; where they do, prefer the nameplate figure.

The current from this conversion is the starting point for circuit design, not the end of it: the design current feeds into device selection, cable sizing with correction factors and voltage drop checks.

Frequently asked questions

How many amps is 9.5kW at 230V?

For a resistive load at power factor 1: 9500 / 230 ≈ 41.3A. That is the arithmetic behind a 9.5kW shower needing a 40A or 45A circuit — and why the cable and device must be sized for the shower's actual rating at nominal voltage.

How do I convert kW to amps on three phase?

Divide the power in watts by √3 × 400 × power factor. For example, 15kW at unity power factor on a 400V three-phase supply draws 15000 / (1.732 × 400) ≈ 21.7A per line. At a power factor of 0.8 the same output needs about 27A per line.

What power factor should I use?

Use 1 for resistive loads — showers, immersion heaters, radiant heating. Motors typically run between 0.8 and 0.9 at full load, and the nameplate value is the one to use where available. A lower power factor means more current for the same kW, so guessing high on pf undersizes the circuit.

Is three-phase current per phase or total?

The calculated figure is the line current — the current flowing in each of the three line conductors for a balanced load. It is not divided by three or summed across phases; each phase conductor and its protective device sees that current.

Want more work coming in?

TradePlanr Agency builds custom-coded, SEO-optimised websites and runs Google Ads for UK trades — from £375, by the team behind TradePlanr.

Explore TradePlanr Agency
Start Now — It's Free

Free to start · No card · No download needed — works in your browser

Download on the App StoreGet it on Google Play